FG Wilson Diesel Power Generator P200-3 144 kW - 175 kW without Housing
zoom_out_map
chevron_left chevron_right

FG Wilson Diesel Power Generator P200-3 144 kW - 175 kW without Housing

Discover the power and dependability of the FG Wilson Power Generator Diesel P200-3, offering an impressive output range of 144 kW to 175 kW. This generator is perfect for various applications and comes without housing, allowing custom installation to suit your needs. Built with durability in mind, you can count on the P200-3 to provide a reliable power source for your essential operations. Enjoy easy installation and maintenance with this powerful and reliable generator, designed to meet your diverse power needs.
$25,270.90
Tax included

20545.45 $ net price (non-EU countries)

100% secure payments

Anatolii Livashevskyi
Product Manager
Українська / Polski
+48721808900
+48721808900
Telegram +48721808900
[email protected]

Olesia Ushakova
Product Manager
Українська / Polski
+48695005004
+48695005004
Telegram +48695005004
[email protected]

Description

The 24 - 220 kVA range provides reliable power for today's world with a competitive offering that delivers everything you need. Providing unrivalled quality, the 24 - 220 kVA range of products offers a trusted performance with an enhanced choice of options, optimising the range for a variety of diverse applications and environments. Designed with the demands of today's world in mind, this range will deliver power solutions in all sectors, from industry and retail to finance and healthcare.

Benefits

Low running costs Fuel Optimised Low running costs

Designed to deliver optimal fuel economy

Choice of Options Enhanced Choice of options

Optimising the range for a variety of diverse applications and environments



Product Specifications For P200-3

Generator Set Specifications

Minimum Rating 180 kVA / 144 kW

Maximum Rating 218.8 kVA / 175 kW

Emissions/Fuel Strategy Fuel Optimised

50 Hz Prime 180 kVA / 144 kW

50 Hz Standby 200 kVA / 160 kW

60 Hz Prime 200 kVA / 160 kW

60 Hz Standby 218.8 kVA / 175 kW

Frequency 50 / 60 Hz

Speed 1500 or 1800 RPM

Voltage 110-480 Volts

50 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.

60 Hz Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).

50 Hz Standby Rating Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.

Engine Specifications

Engine Model Perkins® 1106A-70TAG3

Bore 105 mm (4.1 in)

Stroke 135 mm (5.3 in)

Governor Type Mechanical

Displacement 7.0l (427.8 cu. in)

Compression Ratio 16.0:1

Data sheet

DIKE475P3S

Buy a generator in Poland

The cost of delivery is calculated according to the place of delivery in Poland, Ukraine and European Union.